Air quality in teaching environments at the Institute of Architecture and Urbanism and Design of the Federal University of Ceará

Authors

DOI:

https://doi.org/10.46421/entac.v21i1.8300

Keywords:

Air quality, Carbon dioxide, Particulate matter, Teaching environments, Environmental comfort

Abstract

Carbon dioxide (CO₂) levels and suspended particulate matter (PM2.5 and PM10) were monitored in situ during two monitoring periods of teaching activities in three spaces of the Institute of Architecture, Urbanism and Design at the Federal University of Ceará: the computer laboratory (LABCAD), Classroom 1, and a design studio (Room 7). LABCAD reached  highest CO₂ concentrations, exceeding acceptable conditions up to 93% of the monitored time. Classrooms 1 and 7 showed lower values. Particulate matter concentrations remained within acceptable limits in all three environments, being lower in LABCAD and higher in Classrooms 1 and 7. The results highlight the influence of occupancy density, spatial dimensions, and the characteristics of openings as key determinants of indoor air quality. 

 

Author Biographies

  • Renan Cid Varela Leite, Federal University of Ceará

    Doutorado em Arquitetura e Urbanismo pela Universidade de São Paulo. Professor Adjunto no Instituto de Arquitetura e Urbanismo e Design da Universidade Federal do Ceará

  • Micaele Sousa Lima, Federal University of Ceará

    Cursando Arquitetura e Urbanismos na Universidade Federal do Ceará (Fortaleza - CE, Brasil)

  • Ana Beatriz Mourão Ferreira Gomes, Federal University of Ceará

    Cursando Arquitetura e Urbanismos na Universidade Federal do Ceará (Fortaleza - CE, Brasil)

References

[1] MOHAMAD, A., BURCIN, B., SIMI, H; ZHENG, O; PEDRIELLI, G., WEN, J., WU, T., Ten questions concerning occupant health in buildings during normal operations and extreme events including the COVID-19 pandemic. Building and Environment, Volume 188, 2021, 107480, ISSN 0360-1323, ‘https://doi.org/10.1016/j.buildenv.2020.107480

[2] ARAÚJO, E.; SANTOS, T. C. de. Qualidade do ar em alerta: análise comparativa dos níveis críticos e planos de emergência entre o Brasil e oito países. Instituto Ar, Instituto Alana: São Paulo, 2024.

[3] AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING ENGINEERS. ANSI/ASHRAE STANDARD 62.1-2013: Ventilation for Acceptable Indoor Air Quality. Atlanta: ASHRAE, 2013. 58 p.

[4] __________. ASHRAE Addendum p to ANSI/ASHRAE Standard 62.1-2013, Ventilation for Acceptable Indoor Air Quality. 2015. Disponível em:: https://www.ashrae.org/technical-resources/bookstore/ashrae-standard-241-control-of-infectious-aerosols. Acesso em: 28 de abr. de 2025

[5] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 16401-3: Instalações de ar-condicionado - Sistemas centrais e unitários: parte 3: Qualidade do ar interior. Rio de Janeiro, 2008.

[6] ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 17037: Qualidade do ar interior em ambientes não residenciais climatizados artificialmente - Padrões referenciais. Rio de Janeiro, 2023.

[7] GOBBI, M. E. Normas e regulamentos brasileiros relacionados com qualidade do ar interior e a construção civil. In: ENCONTRO NACIONAL DA ASSOCIAÇÃO NACIONAL DE PESQUISA E PÓS-GRADUAÇÃO EM ARQUITETURA E URBANISMO – ENANPARQ, 8., 2024, Rio de Janeiro. Anais... Rio de Janeiro: ANPARQ, 2024.

[8] ASHRAE. ANSI/ASHRAE Standard 62-1989: Ventilation for Acceptable Indoor Air Quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, 1989.

[9] ASHRAE. ANSI/ASHRAE Standard 62-1999: Ventilation for Acceptable Indoor Air Quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, 1999.

[10] PERSILY, A. Quit blaming ASHRAE standard 62.1 for 1000 ppm CO2. 16th Conference of the International Society of Indoor Air Quality and ClimateOnline. Paper ID ABS-0445, 2000.

[11] STUMM, R. E. Revisiting the 1,000 ppm CO₂ limit. ASHRAE Journal, Atlanta, v. 64, n. 6, p. 18–23, jun. 2022. Disponível em: PDF da technical feature. Acesso em: 13 maio 2026.

[12] FLOSS, M., ZANDAVALLI, R. Bl, LEÃO, J.R.B., CAMILA VESCOVI LIMA CV, VIANNA N, BARROS EF, SALDIVA PHN. Air pollution: a scoping review for clinical recommendations for family and community medicine. Rev Bras Med Fam Comunidade. 2022;17(44):3038. https://doi.org/10.5712/rbmfc17(44)3038www.rbmfc.org.brISSN 2197-7994.

[13] U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA). Particle Pollution (PM) Basics. Washington, DC, 2016.

[14] SALDIVA P.H.N., LICHTENFELS A.J.F.C., PAIVA P.S.O., BARONE I.A., MARTINS M.A., MASSAD, E., PEREIRA J.C.R., XAVIER V.P., SINGER, J. M., BOHM, G. M. Association between Air Pollution and Mortality Due to Respiratory Diseases in Children in São Paulo, Brazil: A Preliminary Report. Environmental Research. 1994, 65(2), 218–225. https://doi.org/10.1006/enrs.1994.1033.

[15] FRANCESCHINI, P. B.; LIGUORI, I. N.; NEVES, L. O. Avaliação da qualidade do ar interior durante a pandemia de Covid-19 em salas de aula naturalmente ventiladas. In: Anais do XVI Encontro Nacional de Conforto no Ambiente Construído/ XII Encontro Latino-Americano de Conforto no Ambiente Construído. Anais...Palmas(TO) online, 2021. Disponível em: https//www.even3.com.br/anais/encac2021/340096-AVALIACAO-DA-QUALIDADE-DO-AR-INTERIOR-DURANTE-A-PANDEMIA-DE-COVID-19-EM-SALAS-DE-AULA-NATURALMENTE-VENTILADAS. Acesso em: 13/10/2025

[16] SILVA, S. V. de O.; PAGEL, E, C.; B, L. E. G.; MARCONSINI, C. Ventilação natural e qualidade do ar em salas de aula: revisão sistemática da literatura. PARC Pesq. em Arquit. e Constr., Campinas, SP, v. 13, p. e022021, 2022. DOI: http://dx.doi.org/10.20396/parc.v13i00.8666284

[17] SILVA, S. V. de O.; PAGEL, E. C.; S., A. J. Q.; VELTEN, F. B. Percepção da qualidade do ar Interior em salas de aula urbanas: estudo de caso em Vitória-ES. Gestão & Tecnologia de Projetos. São Carlos, v19, n2, 2024. https://doi.org/10.11606/gtp.v19i2.221080

[18] XAVIER, E. L. M.; PAGEL, E. C.; MARTINS, R. S. Renovação do ar em salas de aula climatizadas com ar-condicionado tipo split. Periódico Técnico e Científico Cidades Verdes. Vol. 12, N. 39, 2024

[19] ORGANIZAÇÃO MUNDIAL DA SAÚDE, OMS. How Air Pollution Is Destroying Our Health. Disponível em: Climate Change Indicators in the United States. US Environmental Protection Agency, 2016. Disponível em: https://www.epa.gov/sites/default/files/2016-08/documents/climate_indicators_2016.pdf

[20] ANVISA. (2003). Agência Nacional De Vigilância Sanitária. Resolução - RE Nº 9 de 16 de janeiro de 2003. Orientação Técnica elaborada por Grupo Técnico Assessor sobre Padrões Referenciais de Qualidade do Ar Interior em ambientes climatizados artificialmente de uso público e coletivo. Disponível em: https://bvsms.saude.gov.br/bvs/saudelegis/anvisa/2003/rdc0009_16_01_2003.html. Acesso em: 28 abr. 2025.

Published

2026-10-07

Issue

Section

Conforto Ambiental e Eficiência Energética

How to Cite

LEITE, R. C. V.; LIMA, M. S.; GOMES, A. B. M. F. Air quality in teaching environments at the Institute of Architecture and Urbanism and Design of the Federal University of Ceará. NATIONAL MEETING OF BUILT ENVIRONMENT TECHNOLOGY, v. 21, n. 1, 7 Oct.2026.