Hybrid Systems vs. Artificial Cooling

The Case of the Porto Seguro Building, São Paulo

Authors

DOI:

https://doi.org/10.46421/entac.v21i1.8921

Keywords:

Hybrid ventilation, Building Energy Efficiency, Adaptive thermal comfort, building simulation, coorporate buildings

Abstract

This study evaluates the performance of hybrid systems (natural ventilation integrated with HVAC) as a consumption mitigation strategy, using the Porto Seguro Matriz building as a case study. The methodology consisted of computer simulations using EnergyPlus software, comparing three scenarios for the Porto Seguro Matriz building: exclusive natural ventilation, HVAC, and a hybrid system (Vent + HVAC). São Paulo climate data and the RTC adaptive comfort model were employed. The results reveal that hybrid operation not only ensures 100% of hours in thermal comfort but also reduces energy consumption by 52%, generating an annual saving exceeding R$ 1.6 million. It is concluded that the transition to hybrid systems is technically feasible and economically imperative for the high-end real estate sector.

Published

2026-09-06

Issue

Section

Conforto Ambiental e Eficiência Energética

How to Cite

ABREU-HARBICH, L. Hybrid Systems vs. Artificial Cooling: The Case of the Porto Seguro Building, São Paulo. NATIONAL MEETING OF BUILT ENVIRONMENT TECHNOLOGY, v. 21, n. 1, 6 Sept.2026.