ANÁLISE DE CONFORMIDADE DOS SISTEMAS PREVENTIVOS DE COMBATE A INCÊNDIO DE UMA INSTITUIÇÃO DE ENSINO
DOI:
https://doi.org/10.46421/sispred.v4.7931Keywords:
projeto preventivo de incêndio, edifício público, segurança contra incêndioAbstract
This paper presents the Fire Safety Systems and Measures (SMSCI) conformity assessment in an educational building of the Federal University of Santa Catarina (UFSC) on the Florianópolis campus. The study aimed to verify the suitability of the systems installed - fire extinguishers, emergency lighting, fire exit signs, fire alarm and fire-fighting pipes - to the standards in force, comparing the criteria of NSCI 94, in force at the time of the project, with the updated Normative Instructions (IN) of the Santa Catarina Military Fire Brigade (CBMSC). The methodology included on-site inspections and the application of normative checklists. The results indicated adequate overall coverage but revealed specific flaws that compromise the effectiveness of the systems, such as depressurised fire extinguishers, inoperative lighting and signs, access obstructions and a lack of standardisation. The inactive battery plant in block B was identified as a critical point, directly affecting the lighting and signalling systems. The analysis reinforces the importance of ongoing maintenance, standardisation of installations and updating projects in line with current regulations to guarantee the safety of users and the protection of assets. The study also proposes suggestions for future research into fire safety in public buildings.
Downloads
References
ABNT – ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 13860: Glossário de termos relacionados com a segurança contra incêndio. Rio de Janeiro, 1991.
AMA, H.; SUWANCHATREE, S.; MUADCHIM, M.; PRADABPHETRAT, P. Building fire safety assessment: a case study of a university building in the lower south. Safety & Environment Review, v. 6, n. 1, p. 1–6, 2024.
BRASIL. Lei no 13.425, de 30 de março de 2017. Estabelece diretrizes sobre medidas de prevenção e combate a incêndio. *Diário Oficial da União: seção 1*, Brasília, DF, 31 mar. 2017.
BRASIL. Portaria no 108, de 12 de julho de 2019. Aprova o Modelo Nacional de Regulamento de Segurança Contra Incêndios e Emergências. Brasília, DF: Diário Oficial da União, 15 jul. 2019.
CBMSC - CORPO DE BOMBEIRO MILITAR DE SANTA CATARINA. IN 1 (Parte 1) – Procedimentos administrativos. Instrução Normativa de, 24 de abril de 2024. Florianópolis, SC.
GUIPING, P. Innovative research on fire safety management mechanism in colleges and universities based on big data. Proceedings of the 2nd International Conference on Emergency Management and Social Safety (EMSS 2022), p. 186–192, 2019.
ISO - INTERNATIONAL ORGANIZATIONS FOR STANDARDIZATION. ISO 8421-1:1987 – Fire Protection – Vocabulary – Part 1: General terms and phenomena of fire. Londres, 1987.
ONO, R. Parâmetros para garantia da qualidade do projeto de segurança contra incêndio em edifícios altos. Ambiente Construído, Porto Alegre, v. 7, n. 1, p. 97–113, 2007.
SEITO, A. I.; GILL, A. A.; PANNONI, F. D.; ONO, R.; SILVA, S. B.; CARLO, U. D.; SILVA, V. P. A Segurança contra incêndio no Brasil. São Paulo: Projeto Editora, 2008.
UFSC. Universidade Federal do Estado de Santa Catarina. Secretaria de Planejamento. Coordenadoria de Projetos. “Recuperação do espaço físico e da infraestrutura da Universidade Federal de Santa Catarina, destruído pelo incêndio”, Florianópolis, 1996. Disponível em: https://ecv.paginas.ufsc.br/files/2017/05/Hist%C3%B3rico_Inc%C3%AAndio-Pavilh%C3%A3o_ECV.pdf